Practice Ohmic Resistance of Windings

15,244 views

Rolando Leal

Published on Aug 4, 2022
About :

With the ohmic resistance test of transformer coils, it is more common to find problems in the mechanical connections between the bushings and the windings (coils on the primary or secondary side). A false connection can cause high temperatures that “burn” the surrounding insulation and contaminate the dielectric oil with combustible gases. We also perform the ohmic resistance test of the coils to detect possible damage between the insulation of the turns (in this sense it is a complementary test to the transformation ratio tests). This is because when there are turns in short circuit, the ohmic resistance of the winding will be very different with respect to another winding of the same transformer. Although the ohmic resistance values ​​of the windings are very different from the ohmic resistance values ​​of contacts (such as those of the blades, disconnectors or switches), the measurement principle is the same and the interpretation of the results is similar. If you do not yet have the theoretical basis of the ohmic resistance test, I recommend you watch the following video: • Ohmic Resistance Test of Conta... Regarding the reference standard used, you can consult the following standards: • SOM-3531 Reference Standard of the Federal Electricity Commission (CFE: Mexican electric company) Item 3.7 OHM RESISTANCE TEST FOR WINDINGS. “The current used in the measurement must not exceed 15% of the nominal value of the winding, since higher values ​​may obtain inaccurate results caused by variations in resistance due to heating of the winding” • SOM-3531 Item 3.8.5 “To date, variations in the plate impedance of the transformer are evaluated; • IEEE Std 62. Item 6.1.1 Winding resistance “The interpretation of the results is generally based on a comparison of the measurements made separately in each phase in the case of a star-connected winding or between pairs of terminals in a delta-connected winding. A comparison with the original data measured at the factory can also be made. Agreement within 5% for any of the above comparisons is generally considered satisfactory.” • IEEE Std 62. Item 6.1.1.1.1 Voltmeter-ammeter method “The currents used for these measurements normally do not exceed 15% of the nominal current. This avoids heating the winding and therefore changing its resistance. The resistance variation shall not exceed 5% from phase to phase.” • NETA – MTS Item 7.2.2.7 Test values: electrical “7. Temperature-corrected winding resistance values ​​shall be compared within one percent of previously obtained results.”

Trend Videos
4:03
680,204 views   1 day ago
28:38
28:38
3:25
1,140,502 views   5 days ago
4:03
680,204 views   1 day ago
3:34
480,729 views   2 days ago
Google AdSense
336 x 280
Up Next
54:57
CNT Workshop Team
24,214 views
2 years ago
5:43
42:59
CNT Workshop Team
191,722 views
4 years ago
55:53
Jahaziel - Experto en Autos que NO prenden
45,603 views
Streamed 1 year ago
1:00:03
Teda electrónica automotriz
6,175 views
6 months ago
47:26
CNT Workshop Team
94,162 views
3 years ago
50:53
CEDICA Capacitación en Autotrónica
26,046 views
2 years ago
25:15
55:00
CNT Workshop Team
143,373 views
4 years ago
18:37
GARVIN SANDREA PARIS
31,723 views
10 months ago
54:30
CNT Workshop Team
42,333 views
3 years ago
1:01:17
SENATI - Campus Online
277,258 views
7 years ago
31:11
FD AUTOMOTRIZ C.A. (Caracas)
107,644 views
5 years ago
46:20
15:08
1:00:03
Teda electrónica automotriz
6,175 views
6 months ago
59:25
Electronica y Servicio
4,416 views
11 months ago
47:44
Xavi Chiavon
33 views
9 days ago
33:58
33:14
GARVIN SANDREA PARIS
25,244 views
Streamed 3 years ago
54:30
CNT Workshop Team
42,333 views
3 years ago
45:31
CNT Workshop Team
6,564 views
3 years ago
40:00
Elecktro fe2
327,130 views
10 years ago
17:45
J. Jesús Valencia
59,355 views
3 years ago
29:51
Juan Pablo Labanda Valverde
18 views
5 days ago
2:02:47
GARVIN SANDREA PARIS
425,122 views
3 years ago
Google AdSense
336 x 280

fetery.com. Copyright 2024